COM PROFIBUS


Bus Parameters

Bus Description:PROFIBUS
Bus Profile:PROFIBUS DP
Baud Rate:1.5 MBaud

ParameterValueUnitParameter description
T_qui0t_bitQuiet time for modulator/repeater changeover time
T_Slot_eff200t_bitWaiting time for receive
T_Set1t_bitTrigger time after interrupt
Retry Limit1 Message repeats
Gap Factor10 Update factor for PROFIBUS Address area check
Delta-Ttr0t_bitAdditional Ttr caused by external systems
HSA1 Highest PROFIBUS Address of an active station
T_sdr_min11t_bitProtocol processing time
T_sdr_max100t_bitProtocol processing time
T_rdy11t_bitStandby time for acknowledgment
T_id137t_bitIdle time after receiving response
T_id2100t_bitIdle time after sending call without receive
Ttr27201t_bitTotal on-bus Ttr
Typical data cycle time0.0072sTypical data cycle time
Maximum data cycle time0.0544sMaximum data cycle time
Response Monitoring0.1356sMinimum required value
Number of OLMs/OBTs0 Number of OLMs or OBTs included in the bus parameter calculation
Number of repeaters0 Number of repeaters included in the bus parameter calculation
Line length (Cu)0mLength of the copper line included in the bus parameter calculation
Line length (FO)0mLength of the fiber-optic line included in the bus parameter calculation