"PLC1_PT641","NULL","kPa","geen","geen","geen","geen","geen","geen","geen","geen",1
"PLC1_FT641","NULL","m³/h","geen","geen","geen","geen","geen","geen","geen","geen",2
"PLC1_QT641","NULL","NTU","geen","geen","geen","geen","geen","geen","geen","geen",3
"PLC1_LT601","NULL","m","geen","geen","geen","geen","geen","geen","geen","geen",4
"PLC1_PT501","NULL","kPa","geen","geen","geen","geen","geen","geen","geen","geen",5
"PLC1_FT501","NULL","m³/h","geen","geen","geen","geen","geen","geen","geen","geen",6
"PLC1_S640_AlwPri[1]","NULL","Vuldruk te laag","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",7
"PLC1_S640_AlwPri[2]","NULL","Storingscontact FT641","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",8
"PLC1_S640_AlwPri[3]","NULL","Storingscontact QT641","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",9
"PLC1_ALG_AlwPri[1]","NULL","plc configuratie fout","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",10
"PLC1_ALG_AlwPri[2]","NULL","plc batterij leeg","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",11
"PLC1_ALG_AlwPri[3]","NULL","plc kaart storing","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",12
"PLC1_QT501","NULL","NTU","geen","geen","geen","geen","geen","geen","geen","geen",13
"PLC1_S600_AlwPri[1]","NULL","Verzamelstoring XV601","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",14
"PLC1_S600_AlwPri[2]","NULL","Verzamelstoring XV602","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",15
"PLC1_S500_AlwPri[1]","NULL","Verzamelstoring XV501","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",16
"PLC1_ALG_AlwPri[4]","NULL","Comm storing","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",17
"PLC1_S500_AlwPri[2]","NULL","Storingscontact FT501","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",18
"PLC1_S500_AlwPri[3]","NULL","Storingscontact QT501","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",19
"PLC1_S500_AlwPri[4]","NULL","Onvoldoende kelderverversing","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",20
"PLC1_S500_AlwPri[5]","NULL","Leidingbreuk","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",21
"PLC1_PLC_AlwPri[1]","NULL","Storing stuurstroom 24VDC algemeen","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",22
"PLC1_PLC_AlwPri[2]","NULL","Storing stuurstroom 24VDC HV01 lades","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",23
"PLC1_PLC_AlwPri[3]","NULL","Storing stuurstroom 24VDC afsluiters","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",24
"PLC1_PLC_AlwPri[4]","NULL","Storing voedingen 230VAC BK01","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",25
"PLC1_PLC_AlwPri[5]","NULL","Storing voeding 24VDC BK01","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",26
"PLC1_PLC_AlwPri[6]","NULL","Storing voeding 24VDC PLC","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",27
"PLC1_PLC_AlwPri[7]","NULL","Storing voedingen 24VDC metingen","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",28
"PLC1_PLC_AlwPri[8]","NULL","BK01 hoofdschakelaar voeding uit","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",29
"PLC1_PLC_AlwPri[9]","NULL","BK01 hoofdschakelaar storing voeding","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",30
"PLC1_PLC_AlwPri[10]","NULL","LV01 voeding uit","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",31
"PLC1_PLC_AlwPri[11]","NULL","LV01 voeding storing","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",32
"PLC1_PLC_AlwPri[12]","NULL","Verzamelstoring 1 vaste voeding MCC","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",33
"PLC1_PLC_AlwPri[13]","NULL","Verzamelstoring 2 vaste voeding MCC","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",34
"PLC1_S500_AlwPri[6]","NULL","Druk te laag bij debietregeling","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",35
"PLC1_Netw_AlwPri[1]","NULL","Netwachter kabelzijde voedingsveld trafo","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",36
"PLC1_Netw_AlwPri[2]","NULL","Netwachter railzijde","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",37
"PLC1_Netw_AlwPri[3]","NULL","Netwachter overspanning voedingsveld trafo","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",38
"PLC1_Netw_AlwPri[4]","NULL","Netwachter storing stuurspanning","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",39
"PLC1_Netw_AlwPri[5]","NULL","Netwachter lastschakelaar Uit","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",40
"PLC1_Netw_AlwPri[6]","NULL","Netwachter 2 kabelzijde voedingsveld generator","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",41
"PLC1_Netw_AlwPri[7]","NULL","Netwachter 2 overspanning voedingsveld generator","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",42
"PLC1_Netw_AlwPri[8]","NULL","Netwachter 2 storing stuurspanning","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",43
"PLC1_Netw_AlwPri[9]","NULL","Netwachter 2 lastschakelaar Uit","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",44
"PLC1_FS641_AlwPri[1]","NULL","Stromingsdetectie reinwater","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",45
"PLC1_FS504_AlwPri[1]","NULL","Stromingsdetectie reinwater","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",46
"PLC1_LS651_AlwPri[1]","NULL","Water op Vloer","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",47
"PLC1_LS652_AlwPri[1]","NULL","Water op Vloer","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",48
"PLC1_LS653_AlwPri[1]","NULL","Niveaudetectie","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",49
"PLC1_TS971_AlwPri[1]","NULL","Thermostaat","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",50
"PLC1_TS972_AlwPri[1]","NULL","Thermostaat","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",51
"PLC1_X103_AlwPri[1]","NULL","Airco","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",52
"PLC1_X104_AlwPri[1]","NULL","Airco","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",53
"PLC1_PT642","NULL","kPa","geen","geen","geen","geen","geen","geen","geen","geen",54
"PLC1_LT602","NULL","m","geen","geen","geen","geen","geen","geen","geen","geen",55
"PLC1_PT502","NULL","kPa","geen","geen","geen","geen","geen","geen","geen","geen",56
"PLC1_S640_AlwPri[4]","NULL","Verzamelstoring XV502","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",57
"PLC1_S500_AlwPri[7]","NULL","Onvoldoende ververst bij debietregeling","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",58
"PLC1_S500_AlwPri[8]","NULL","2 of meer distributiepompen in storing","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",59
"PLC1_PLC_AlwPri[14]","NULL","Storing 24Vdc UPS","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",60
"PLC1_PLC_AlwPri[15]","NULL","Storing 24Vdc UP02","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",61
"PLC1_HOST_01_AlwPri[1]","NULL","Host watchdog alarm","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",65
"PLC1_HOST_02_AlwPri[1]","NULL","Host intern actief","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",66
"PLC1_HOST_00_AlwPri[1]","NULL","Host uit, let op andere WPB's","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",67
"PLC1_HOST_00_AlwPri[2]","NULL","Host afwijkende reinwater druk","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",68
"PLC1_HOST_00_AlwPri[3]","NULL","Host afwijking reinwater debiet","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",69
"PLC1_HOST_00_AlwPri[4]","NULL","Host niet beschikbaar","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",70
"PLC1_HOST_00_AlwPri[5]","NULL","Host debietsetpoint begrensd op max","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",71
"PLC1_HOST_00_AlwPri[6]","NULL","Host debietsetpoint begrensd op min","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",72
"PLC1_HOST_00_AlwPri[7]","NULL","Host leidingbreuk verbruiksgebied","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",73
"PLC1_HOST_03_AlwPri[1]","NULL","Inname en distributie actief","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",74
"PLC1_PROGN_01_AlwPri[1]","NULL","Keldergrenzen overschreden","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",62
"PLC1_PROGN_02_AlwPri[1]","NULL","Prognose niet beschikbaar","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",63
"PLC1_PROGN_00_AlwPri[1]","NULL","Prognose watchdog alarm","NULL","NULL","NULL","NULL","NULL","NULL","NULL","NULL",64